Demand Controlled Ventilation: Use in Calgary and Impact of Sensor Location

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

Demand controlled ventilation (DCV) is used to reduce the amount of energy required to condition outdoor air introduced into a building based by monitoring occupancy. This thesis reports the hours DCV is used in an existing building in Calgary. Results showed DCV was used approximately 20% of annual fan operating hours when paired with an air-side economizer and just over 60% when a heat recovery wheel was part of the system. A Simulink model was built to compare the performance of two currently used DCV approaches based on carbon dioxide readings (CO2-DCV). The model showed positioning a sensor in the supply air duct (SACO2-DCV) to serve multiple zones of a re-circulating system maintained lower CO2 levels when occupancy varied between rooms than if the sensor were in the return-air duct (RACO2-DCV). The model showed these lower CO2 levels were due to SACO2-DCV over-ventilating spaces relative to typical requirements.

Description

Keywords

Citation

Lachapelle, A. (2012). Demand Controlled Ventilation: Use in Calgary and Impact of Sensor Location (Master's thesis, University of Calgary, Calgary, Canada). Retrieved from https://prism.ucalgary.ca. doi:10.11575/PRISM/25548